Data record std.ieee-1547.voltage-trip-range-rule

Verified 2026-10-24 Confidence: High

Clause 6.4.1 of IEEE 1547-2018 explains how its ranges of allowable settings are to be read: within every clearing-time range and within the overvoltage ranges the lower bound may never be undercut while the upper bound may be exceeded, whereas within the undervoltage ranges it is the upper bound that may never be exceeded; a setting beyond a range is tolerated solely to protect equipment and may not conflict with the ride-through requirements of clause 6.4.2.

ProvenanceIEEE 1547-2018 supports data record std.ieee-1547.voltage-trip-range-rule, which is cited on the entry IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces.SOURCEIEEE 1547-2018IEEE 1547-2018Licensed standard, clause 6.4.1, footnote bDATA RECORDstd.ieee-1547.voltage-trip-range-rulestd.ieee-1547.voltage-tr..Verified 2026-10-24ENTRYIEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems InterfacesIEEE Standard for Interc..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 1547-2018Licensed standard, clause 6.4.1, footnote b
Data recordstd.ieee-1547.voltage-trip-range-ruleVerified 2026-10-24
EntryIEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems InterfacesNo revisions
Subject
IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces (Standards)
Kind
Standard scope
Source
IEEE 1547-2018, clause 6.4.1, footnote b, Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.ieee-1547.voltage-trip-range-rule." Interconnection Reference. 2026-10-24. https://www.interconnectionreference.com/data/std.ieee-1547.voltage-trip-range-rule/.