Data record std.ieee-1547-9.structure.ride-through-exceptions

Verified 2026-10-24 Confidence: Medium

Clauses 6.4.2 and 6.5.2.1 of IEEE 1547.9-2022 explain that the small-export ride-through exception of IEEE 1547-2018 is judged at the maximum exporting power point of a modulating energy storage DER, and that where a Category III unit is meant to go on serving its load through an unplanned transition to an island, the Area EPS operator and the DER operator may agree a momentary cessation response time that is longer than the value in the base standard's table.

ProvenanceIEEE 1547.9-2022 supports data record std.ieee-1547-9.structure.ride-through-exceptions, which is cited on the entry IEEE Guide for Using IEEE Std 1547 for Interconnection of Energy Storage Distributed Energy Resources with Electric Power Systems.SOURCEIEEE 1547.9-2022IEEE 1547.9-2022Licensed standard, clause 6.4.2, 6.5.2.1DATA RECORDstd.ieee-1547-9.structure.ride-through-exceptionsstd.ieee-1547-9.structur..Verified 2026-10-24ENTRYIEEE Guide for Using IEEE Std 1547 for Interconnection of Energy Storage Distributed Energy Resources with Electric Power SystemsIEEE Guide for Using IEE..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 1547.9-2022Licensed standard, clause 6.4.2, 6.5.2.1
Data recordstd.ieee-1547-9.structure.ride-through-exceptionsVerified 2026-10-24
EntryIEEE Guide for Using IEEE Std 1547 for Interconnection of Energy Storage Distributed Energy Resources with Electric Power SystemsNo revisions
Subject
IEEE Guide for Using IEEE Std 1547 for Interconnection of Energy Storage Distributed Energy Resources with Electric Power Systems (Standards)
Kind
Standard scope
Source
IEEE 1547.9-2022, clause 6.4.2, 6.5.2.1, Guide to Using IEEE 1547 for Interconnection of Energy Storage Distributed Energy Resources, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.ieee-1547-9.structure.ride-through-exceptions." Interconnection Reference. 2026-10-24. https://www.interconnectionreference.com/data/std.ieee-1547-9.structure.ride-through-exceptions/.