Data record std.ieee-1547-1.definition.clearing-time

Verified 2026-10-24 Confidence: High

Annex A.2 of IEEE 1547.1-2020 defines clearing time as the interval from the start of the abnormal condition until the DER ceases to energize the Area EPS, made up of detection time, any adjustable delay, the interposing device operating and arcing time, and the interrupting device time. The trip time, which starts at the leading zero crossing in the first half cycle where the parameter is beyond its limit, can be either a part of the clearing time or equal to it; every normative requirement is expressed as a clearing time.

ProvenanceIEEE 1547.1-2020 supports data record std.ieee-1547-1.definition.clearing-time, which is cited on the entry IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces.SOURCEIEEE 1547.1-2020IEEE 1547.1-2020Licensed standard, clause A.2DATA RECORDstd.ieee-1547-1.definition.clearing-timestd.ieee-1547-1.definiti..Verified 2026-10-24ENTRYIEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated InterfacesIEEE Standard Conformanc..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 1547.1-2020Licensed standard, clause A.2
Data recordstd.ieee-1547-1.definition.clearing-timeVerified 2026-10-24
EntryIEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated InterfacesNo revisions
Subject
IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources with Electric Power Systems and Associated Interfaces (Standards)
Kind
Definition
Source
IEEE 1547.1-2020, clause A.2, Conformance Test Procedures for Equipment Interconnecting Distributed Energy Resources, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.ieee-1547-1.definition.clearing-time." Interconnection Reference. 2026-10-24. https://www.interconnectionreference.com/data/std.ieee-1547-1.definition.clearing-time/.